Survey of hot water temperatures in campgrounds:
elevated scalding risk and energy wastage
The epidemiology of scalding injuries in New Zealanders
(particularly children) and the need for prevention has been detailed by health
professionals for over three decades. There have been articles published in the
1970s,1 the
1980s,2–5 the
1990s6,7 and in the current
century.8–10
A recent study identified a total of 1015 hospital
admissions for 862 tap water burn events in New Zealand from 2000 to
2009.11 Combined with these persisting health
concerns are the growing need to use electricity more efficiently to reduce
running costs and to lower the greenhouse gas emissions which contribute to
climate change.
At present the New Zealand Building Code 1992
specifies that stored hot water in residential dwellings should be held at
temperatures greater than 60ºC (irrespective of whether a mixing device is
installed) so as to kill the micro-organism, Legionella. The Code also
specifies that this hot water should be delivered at not more than 55ºC (or
45ºC for retirement homes and early childhood education centres), so as to
reduce the risk of scalding.
Given this background we aimed to expand the study of New
Zealand hot water temperatures from the previous studies in domestic settings,
to an unstudied public setting: i.e., public campgrounds. In particular, we
aimed to: (i) assess the extent of hazardous water temperatures (i.e., scalding
risk) in sanitary fixtures used for personal hygiene in a sample of New Zealand
campgrounds; and (ii) to assess the potential for further energy savings in
these settings.
Methods—Convenience sampling was
performed involving 25 New Zealand campgrounds that three of the authors
holidayed in over a 4-year period (i.e. while participating in cycle touring
holidays). The public campgrounds were located in both main islands and in the
following regions: Southland/Otago/Canterbury (n=8, February 2008), Otago (n=5,
December 2008), Northland (n=4, December 2009), Waikato (n=4, December 2010),
and Otago/Southland (n=4, December 2011). Sampling was mainly performed by one
author (NW) but also by another (JJ).
We measured the temperature of hot water: (i) that was
running into a basin in the men’s toilet block (maximum temperature
reached within 5 minutes); and (ii) in the men’s shower with just the hot
tap flowing (recording maximum temperature). We aimed to measure the temperature
as close to 1600h on day of arrival at the campground and as close as possible
to 0700h on the following day of departure. A thermometer with range of up to
150 degrees Celsius (°C) and accurate to within 0.1°C was used (a LCD
digital pen type stem thermometer [ST-9282], Winning Technology Ltd, China).
This thermometer showed no indication of any performance problems (based on
regular comparisons with an identical thermometer). Other data collected
included: if wood (wet-back) water heating was used; and if the taps were
labelled hot/cold (words or colour-coding).
Results and Discussion—The key
findings from this study were the relatively high mean and median temperatures
for both taps and showers, with 74% of these temperatures exceeding 55°C,
the maximum level specified in the Building Code (Table 1). The American Academy
of Pediatrics recommend a maximum level of 120°F, equivalent to
48.9°C,12 which was exceeded by 90% of
samples. This lower level (49°C maximum) is also set in certain legislation
(e.g. Washington State, USA) and various codes (the Ontario Building Code, and
the International Plumbing Code).
Although mean hot tap temperatures were slightly higher than
shower temperatures (hot setting), the differences were not statistically
significant. Similarly, there were no statistically significant differences
between morning and evening temperatures for all devices (62.3 vs 62.4°C
respectively) and when analysed by device.
The campgrounds that used wood-fuelled heating systems
(n=3), tended to have hotter water temperatures (means for all devices = 65.1 vs
61.8°C, but with this difference was not statistically significant). Two of
the campgrounds using wood fuel had warning signs in the toilet/shower block
regarding the potentially high water temperatures.
Of note is that reducing hot water storage temperatures is
one of cheapest and most cost-effective energy saving opportunities for hot
water systems. Standing losses (the heat loss to maintain storage temperatures)
in many hot water systems amounts to 30–40% of total hot water energy
consumption. Each 1°C reduction in hot water storage temperature reduces
standing losses by approximately 3%.
For the basin taps, colour-coding (e.g. red for hot, blue
for cold) or word labels were present in 60.7%, partially present (e.g., just
one of two taps coloured or labelled) in 32.1% and completely absent for 7.1%.
For showers, the equivalent figures were: 60.7%, 3.6% and 35.7%
respectively.
These results have various limitations, particularly the
non-random sampling of campgrounds, the modest number of campgrounds sampled
(n=25), and the limited number of samples per campground. Furthermore, sampling
was generally in early December and so was outside the peak season for
campground use. When campground use is high, average hot water temperatures will
probably be lowered as water may be not fully heated to the set temperature.
Nevertheless, it is plausible that some campground operators may respond by
setting temperatures even higher at peak use times. Vulnerable people, such as
children, may use these facilities more often outside the times of peak use, and
therefore be exposed to greater scalding risk.
Ideally further studies would clarify the hot water
situation in New Zealand campgrounds, and better identify the societal optimum
for hot water temperature levels in a range of domestic and public settings.
That is, such work should ideally determine the optimal trade-off between
striving for lower water temperatures (to prevent scalds, save costs and lower
greenhouse gas emissions), with the potential benefits of higher temperatures
(possibly extra convenience and possibly legionellosis
prevention13).
Of note is the uncertain role of hot water systems in
buildings causing legionellosis in New
Zealand,14 and the absence of analytical
evidence for any such relationship in the international
literature.11 Therefore, we suspect that the
current 55°C level in the Building Code is probably too high from health,
economic and societal perspectives. This point has also been articulated by
others in the New Zealand setting.11,15
Furthermore, there are two regulatory approaches which could
be used to ensure that campgrounds reduce the scalding risk (at least to below
the current level in the Building Code):
In
summary, the excessive temperatures identified in this study probably warrant
further action by government agencies on the grounds of reducing the risk of
scalding. Reducing hot water storage temperatures will also contribute to more
efficient use of energy and save fuel costs for campground operators.
Table 1. Sanitary fixture (basin hot tap and
shower) temperatures in 25 New Zealand campgrounds (summer months, 2008 to
2011)*
* Two campgrounds did not have hot taps in the
toilet/shower block facilities. In one campground the basin/shower at a lodge
were also sampled in addition to the communal facilities block. In one other
site a stay of two nights allowed for repeat evening samples. See Methods
section above for other details.
** The 55°C level is the maximum at the tap as in
the current NZ Building Code (1992). The 48.9°C level is that recommended
by the American Academy of Pediatrics (equivalent to 120°F).
Nick Wilson1*, Jonathan
Jarman2, Bill
Brander3, Michael
Keall1
1 Department of Public
Health, University of Otago, Wellington, New Zealand
2 Northland District
Health Board, Whangarei, New Zealand
3 Energy Efficiency
and Conservation Authority, Wellington, New Zealand
* Email: nick.wilson@otago.ac.nz
Competing interests: The authors have
no competing interests and there was no funding for this research. The views
expressed are those of the authors and do not necessarily represent the agencies
that employ them.